Rating of Air Compressors and Air Equipment
Common terms rating
air flow capacity are-
1.
CFM
- CFM (Cubic
Feet per Minute) is the imperial method of describing the volume flow rate
of compressed air. It must be defined further to take account of pressure,
temperature and relative humidity - see below.
2.
ICFM
- ICFM (Inlet
CFM) rating is used to measure air flow in CFM (ft3/min) as it
enters the air compressor intake.
3.
ACFM
- ACFM (Actual CFM) rating is used
to measure air flow in CFM at some reference point at local conditions.
This is the actual volume flow rate in the pipe work after the compressor.
4.
FAD
- FAD (Free Air
Delivery) is the actual quantity of compressed air converted back to the
inlet conditions of the compressor. The units for FAD are CFM in the
imperial system and l/min in the SI system. The units are in general
measured according the ambient inlet standard conditions ISO 1217: Ambient
temperature = 20oC, Ambient pressure
= 1
bar abs, Relative humidity = 0%, Cooling water/air
= 20oC and
Effective working pressure at discharge valve = 7 bar abs.
- 1 m3/min
(FAD) = 1000
liter/min (FAD)
= 1000
dm3/min (FAD)
= 16.7
l/s (FAD)
= 16.7
dm3/s (FAD)
=
35.26 ft3/min (FAD)
5.
ANR
- ANR (Atmosphere Normale de
Reference) is quantity of air at conditions 1.01325 bar absolute, 20oC
and 65% RH.
6.
SCFM
- SCFM
(Standard CFM) is the flow in CFM measured at some reference point but
converted back to standard air conditions (Standard
Reference Atmosphere) 14.696 psia, 60oF.
7.
nl/min
- nl/min is the flow in l/min
measured at some reference point but converted to standard air conditions 1.01325
bar absolute, 0oC and 0% RH .
8.
ISO 1217
- standard
reference ambient conditions - temperature 20oC, pressure 1 bar
abs, relative humidity 0%, cooling air/water 20oC, and working
pressure at outlet 7 bar absolute.
Example - Rating a Compressor
A typical rating of a
compressor may look like this
FAD (CFM) |
Description |
11.1 cfm @ 7.5 Bar |
The Free Air Delivery from the compressor
is |
8.2 cfm @ 10 Bar |
The Free Air Delivery from the compressor
is |
Example:-
Capacity
Assessment of Compressor |
|||||
Procedure |
|||||
• Isolate the compressor along with
its individual receiver being taken for test. |
|||||
• Open drain valve and empty out
the receiver and pipelines. |
|||||
• Start the Compressor and activate
the stopwatch. |
|||||
• Note the time taken to attain the
normal operational pressure P2 (in the receiver) from the initial pressuer
P1. |
|||||
|
|
|
|||
|
PARAMETERS |
UOM |
VALUE |
|
|
QD |
Design Free Air Delivery |
Nm3/Min |
14.75 |
|
|
P2 |
Final Pressure |
Kg/cm2 |
7.03 |
|
|
P1 |
Initial Pressure |
Kg/cm2 |
0.5 |
|
|
P0 |
Atmospheric Pressure |
Kg/cm2 |
1.026 |
|
|
V |
Storage Volume of receiver
including after cooler and pipes |
M3 |
8.322 |
|
|
T |
Time taken to build up pressure P2 |
Min |
4.021 |
|
|
t1 |
Atmospheric Temp. |
°
C |
35 |
|
|
t2 |
Actual Compressed Air Temp. |
°
C |
45 |
|
|
|
|||||
Calculate
the capacity as per the given formula. |
|||||
QA |
Actual Free Air Delivery |
Nm3/Min |
{(P2
- P1 )/ P0} x (V/T) |
13.17 |
|
f |
Correction Factor |
|
(273
+t1)/ (273 + t2) |
0.97 |
|
QC |
Corrected Free Air Delivery |
Nm3/Min |
QA
x f |
12.76 |
|
|
Deviation in Capacity |
% |
(QD
- QC) x 100/QD |
13.50 |
Reference: - engineeringtoolbox.com/rating-air-compressors
Comments
Post a Comment